Data Hall

Operating Environment


  • Room temperature: 23 ± 1℃
  • Relative humidity: 55%
  • Air supply arrangement: underfloor air supply and top air return
  • Emerson precision air conditioners in N+1 configuration, 2N power supply, medium-temperature chilled water system
  • The chilled water system is designed to work in a loop, with A and B pipelines safely and physically separated to work in mutual use and backup mode. The system is equipped with variable-flow secondary pumps in N+1 redundant configuration
  • Magnetic water chiller in N+1 redundant configuration; environmentally friendly and stable
  • 6 storage tanks are used to ensure that the room temperature rise will not exceed 6℃ within 15 minutes
  • Two municipal water pipes, with water storage for supply for more than 48 hours
  • With a total effective capacity of 880 m³, the reservoir stores water for use by the indoor fire hydrants for 2 hours, by the sprinkler system for 1 hour, and for emergency water supply of up to 24 hours
  • Feedwater pumps, drainage pumps, fire pumps in N+1 redundancy
  • Water leakage detection