Data Hall
Operating Environment
- Room temperature: 23 ± 1℃
- Relative humidity: 55%
- Air supply arrangement: underfloor air supply and top air return
- Emerson precision air conditioners in N+1 configuration, 2N power supply, medium-temperature chilled water system
- The chilled water system is designed to work in a loop, with A and B pipelines safely and physically separated to work in mutual use and backup mode. The system is equipped with variable-flow secondary pumps in N+1 redundant configuration
- Magnetic water chiller in N+1 redundant configuration; environmentally friendly and stable
- 6 storage tanks are used to ensure that the room temperature rise will not exceed 6℃ within 15 minutes
- Two municipal water pipes, with water storage for supply for more than 48 hours
- With a total effective capacity of 880 m³, the reservoir stores water for use by the indoor fire hydrants for 2 hours, by the sprinkler system for 1 hour, and for emergency water supply of up to 24 hours
- Feedwater pumps, drainage pumps, fire pumps in N+1 redundancy
- Water leakage detection